Electrical field connections:
IP65 rated Deutsch DT series connectors
Enclosure:
P65 rated metal enclosure
Indications:
Alarm: red LED
Buzzer
Discharged: red LED
Fault: amber LED
Isolated: amber LED
Power: FAULT amber LED
Power: ON green LED
Predischarge: amber and red LEDs
Inputs:
1 detection input suitable for use with Hochiki conventional smoke or thermal detectors, or LHD cable and thermal probes
1 discharge confirmation input (latching)
2 external power inputs – nominal 12 V or 24 V (8 V DC to 30 V DC)
Manual Controls:
ACK/TEST: push button used to:
Test (panel idle): Operates all audible and visual indicators and auxiliary output
Acknowledge: Suppresses audible fault and alarm indications
ARM push button with configurable delay timer periods of: 0 (default), 5, 10, 15, 20, 30, 40 and 60 sec
DIM: Push button used:
In the normal state to adjust the brightness of the LED indicators
In a FAULT state to provide access to the faultfinding diagnostic function (common system faults)
Fault: Fault finding function
Fire System Discharge: Missilestyle switch
FUNC.: Push button used in combination with other panel buttons, allows users to perform additional functions
Isolate: Switch located on panel printed circuit board (PCB).
Used to isolate the discharge output for testing purposes
System Reset: Used to reset panel following fault or alarm indications
Outputs:
1 auxiliary output, rated for 2 amps, – used to switch panel incoming power supply voltage (default configuration). The auxiliary output can be configured if desired to provide a continuous DC power supply of the same voltage as the supply voltage for the panel
1 predischarge alarm output rated for 2 amps – used to switch incoming voltage
1 discharge output, rated for 1 amp, switches incoming panel power supply voltage (supervised for open circuit and earth faults). Capable of activating:
- Up to 3 StatX® aerosol generators, connected in series for 12 volt powered systems
- Up to 8 StatX® aerosol generators for 24 volt powered systems